N041--SPD AHU Replacement Salisbury

Posted Date: Sep 19, 2023
Due Date: Oct 25, 2023
Awarded Date: No Awarded Date
SetAside Type
Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-A
Solicitation ID Solicitation Title Solicitation Office
36C24623Q1012 N041--SPD AHU Replacement Salisbury
Synopsis
N041--SPD AHU Replacement Salisbury .... Read More
Office Location Agency Name Solicitation Base Posting Type
VETERANS AFFAIRS, DEPARTMENT OF Presolicitation
SetAside Type
Solicitation ID Solicitation Title Solicitation Office
36C24623Q1012 N041--SPD AHU Replacement Salisbury
Synopsis
How long can the unit be down to change this out? Over a weekend about 48 hours. What is the insulation specification for duct and piping? Steam for low and medium pressure 1 ½ fiberglass, CW foam 1 ½ , duct 2 wrapped What is the controls sequence for this AHU? Per the MCP for SPD they require positive air flow, humidity between 20-30%, temperature between 66-76 degrees Fahrenheit, and 4 ACH (air changes per hour Please provide a specification on the AHU to include the performance specifications for the unit.  Per the MCP for SPD .... Read More