How long can the unit be down to change this out? Over a weekend about 48 hours. What is the insulation specification for duct and piping? Steam for low and medium pressure 1 ½ fiberglass, CW foam 1 ½ , duct 2 wrapped What is the controls sequence for this AHU? Per the MCP for SPD they require positive air flow, humidity between 20-30%, temperature between 66-76 degrees Fahrenheit, and 4 ACH (air changes per hour Please provide a specification on the AHU to include the performance specifications for the unit.  Per the MCP for SPD .... Read More
|
||